2080-IF2
Electrical
| Number of analogue inputs | 2 |
|---|---|
| Resolution of the analogue inputs | 12 Bit |
| Input, current | Yes |
| Input, voltage | Yes |
| Input, resistor | No |
| Input, resistance thermometer | No |
| Input, thermocouple | No |
| Input signal, configurable | No |
| Output, current | No |
| Output, voltage | No |
| Output signal configurable | No |
| Analogue inputs configurable | Yes |
| Analogue outputs configurable | No |
| Type of electric connection | Screw connection |
| Data range | 0 to 65535 |
| Channel to channel isolation | Non-isolation |
| Update time | 180 ms per enabled channel |
| Input group to bus isolation | No isolation |
| Module error | Voltage: ±1.5% @ over full temperature range, -20…65°C (-4…149°F), Current: ±2.0% @ over full temperature range, -20…65°C (-4…149°F) |
| Wire size | Solid: 0.14 mm2 (26 AWG)…1.5 mm2 (16 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 (26 AWG)…1.0 mm2 (18 AWG) @ Rated @ 90 °C (194 °F) insulation maximum |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Recommended maximum shielded cable length | 10 m |
| Voltage ranges | 0 V |
| Current range | 0 mA |
| Field input calibration | Not required |
| Overall accuracy | Voltage terminal: ±1% full scale @ 25°C, Current terminal: ±1% full scale @ 25°C |
Environmental
| Surrounding air temperature, max | 65 °C |
|---|---|
| North American temperature code | T4 |
| Power consumption | <60 mA @ 3.3V |
| Emissions | CISPR 11 (IEC 61000-6-4): Class A |
| ESD immunity | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges |
| EFT/B immunity | IEC 61000-4-4: ±2 kV @ 5 kHz on shielded ports |
| Relative humidity | IEC 60068-2-30 (Test Db, unpackaged damp heat), 5…95% noncondensing |
| Conducted RF immunity | IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz |
| Surge transient immunity | IEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports |
| Operating temperature | -20…65 °C (-4…149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock) |
| Radiated RF immunity | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz, |
| Operating altitude | 2000 m |
| Nonoperating temperature | -40…85 °C (-40…185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) |
Output Specifications
| Non-linearity | ±0.1% @ in percent full scale |
|---|
General Specifications
| Repeatability | ±0.1% |
|---|
Mechanical
| Vibration | IEC 60068-2-6 (Test Fc, operating), 2 G @ 10…500 Hz |
|---|---|
| Shock | IEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount: 25 g, nonoperating, Panel Mount: 35 g nonoperating |
| Mounting torque | 0.2 Nm |
| Terminal screw torque | 0.22…0.25 Nm (1.95…2.21 lb-in) (using a 2.5 mm (0.10 in.) flat-blade screwdriver) |
Input Specifications
| Input impedance | >100 kΩ for voltage mode, 250 Ω for current mode |
|---|
Certification
| Explosion safety category for gas | None |
|---|---|
| Explosion safety category for dust | None |
| RESOURCE | PUBLICATION NUMBER |
|---|---|
| User Manual | 2080-UM004 |
- Korean Register of Shippin
This product was certified with the above certifications as of 2024-09-02. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.