Kawasaki Thermal Engineering (KTE) has built package boilers in Japan since 1899. Its multi-tube once-through boilers raise steam quickly, take little floor space and match the performance of larger water-tube and fire-tube boilers.
The KF series is Kawasaki’s small once-through boiler for 750–2,000 kg/h equivalent evaporation on natural gas or LPG, suited to small and mid-size plants, hotels and hospitals.
Key features
- 96% efficiency (KF-750/1000) and 98% (KF-1500/2000)
- 3-position firing and 2-position feed water control for simple operation
- 0.98 MPa working pressure, 1.56 or 2.15 MPa optional
- Steam dryness of 99.5% or more from the centrifugal spiral-vane steam separator
- 15-year design life: feed water to the steam separator, built-in deaerator, all pressure parts annealed
- Colour touch-screen operation with colour status lighting
- Links to the Every FIT data logger (up to 16 boilers) and internet remote monitoring
Technical data
| Model | KF-750AGE | KF-1000AGE | KF-1500AGE | KF-2000AGE |
|---|---|---|---|---|
| Equivalent evaporation (kg/h) | 750 | 1,000 | 1,500 | 2,000 |
| Actual evaporation (kg/h) | 629 | 839 | 1,258 | 1,677 |
| Max. working pressure (MPa) | 0.98 (option 1.56 / 2.15) | |||
| Heat transfer surface (m²) | 4.9 | 4.9 | 9.8 | 9.8 |
| Combustion / feed water control | 3 positions / 2 positions | |||
| Fuel | Natural gas (NG), LPG | |||
| Gas supply pressure (MPa) | 0.078–0.294 (NG) | |||
| Boiler efficiency (%) | 96 | 96 | 98 | 98 |
| Fuel consumption (m³N/h) | 43.4 | 57.9 | 85.1 | 113.4 |
| Feed water temperature (°C) | 15–100 | |||
| Holding water (L) | 148 | 148 | 275 | 275 |
| Dry weight (kg) | 1,460 | 1,560 | 2,400 | 2,500 |
| Power supply | AC380V 50Hz 3φ | |||
| Forced draft fan / feed pump (kW) | 2.2 / 0.75 | 5.5 / 1.5 | 5.5 / 1.5 | 7.5 / 2.2 |
| Dimensions L×W×H (mm) | 1,740×1,100×2,187 | 1,740×1,100×2,187 | 2,170×1,150×2,708 | 2,170×1,150×2,714 |
Applications
- Food, beverage and dairy plants: cooking, sterilising, CIP
- Textile dyeing, industrial laundry, paper and packaging
- Chemicals, pharmaceuticals, rubber and plastics
- Hotels, hospitals and buildings needing stable saturated steam
FEYANA support in Vietnam
FEYANA supplies Kawasaki once-through boilers for projects in Vietnam: model and unit-count selection from your steam load, passing technical enquiries to the manufacturer, quotations, delivery follow-up and coordination of installation, commissioning and maintenance. FEYANA can also advise on feed water treatment so the boilers run reliably.
Information to send for a boiler proposal
- Maximum and normal working pressure (MPa)
- Maximum steam demand (kg/h) and feed water temperature (°C)
- Fuel type (NG, LPG, diesel), heating value and gas supply pressure
- Feed water quality and steam usage
- Annual operating hours and load fluctuation
- Site power supply (phase, voltage, frequency)
Data from the Kawasaki Thermal Engineering catalogue (CAT.No.EBI-0201), for reference only. Equivalent evaporation is based on feed water at 100 °C turned into steam at 100 °C; actual evaporation and efficiency are at 0.49 MPa steam pressure, 15 °C feed water and 35 °C room temperature. Specifications may change without notice. Kawasaki is a trademark of Kawasaki Heavy Industries, Ltd.
See other models in Kawasaki Once-Through Boilers. Contact FEYANA for advice and a quotation: WhatsApp +84 988 641 591 – sales.00@feyana.com.